• Mon-Fri 7:30-17:30 I Sat -Sun Closed

Ghaddar Generator DT300 – DT330S (1500 rpm) powered by John Deere

Product description

Ratings @ 0.8 PF

Voltage*

230/400 V

Frequency*

50 Hz

Prime rating

DT300*

300 KVA

Stand-by Rating

DT330S*

330 KVA

Ghaddar Generator DT300 – DT330S (1500 rpm) powered by John Deere

The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.

Notes

  1. The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
  2. This generating set is of fixed speed of 1500 rpm.
  3. DT300 (prime power): variable load and unlimited hour usage with an average load factor of 80% of the prime rating per 24 hours. A 10% overload is permitted for 1 hour in every 12-hour operation.
  4. DT330S (standby power): variable load limited to an annual usage up to 500 hours, with 300 hours of which may be continuous running. No overload is permitted.

Engine Technical Data

Make & Model / GSPUJOHN DEERE 6090HF475
Cylinders & Arrangement6; vertical in-line
Bore & Stroke (mm)106 × 127
Induction systemTurbocharged – air-to-air Aftercooled
 CombustionDirect injection
Cycle4 stroke
Compression ratio16.0:1
Cooling SystemWater cooled
Displacement9.0 liters
Lube oil capacity40 liters Max
Coolant capacity43 liters
Standard governor (Optional)Electronic
Engine Speed1500 rpm

Fuel & Oil Consumption

LoadFuel Cons. (L/H)Oil Cons. (L/H)
100%64.10.186
75%51.10.147
50%34.30.105
25%17.50.053
Radiator Cooling Air Flow (m3/s)8.2
Emissions regulationsEU Stage II
Exhaust temperature (°C, max)587
Max exhaust gas flow (m3/min)57.7
Max. allowed back pressure (kPa)7.5

The above performance data are valid as per the following specs:

  • Diesel Fuel according to BS2869 Class A2 or equivalent.
  • Lubricating oil according to SAE 15W-40 API CI4.
  • Coolant mixture: 50% antifreeze and 50% fresh water.

Alternator Technical Data

Make & ModelLeroy Somer TAL046F
Frequency / No. of poles50 Hz / 4P
Ingress protectionIP23
Insulation classH
Terminals (Optional)6 (12)
Excitation systemSHUNT
Winding pitch2/3
AVR modelR150
Overspeed2250 R.P.M.
Voltage regulation±1%
Coolant air flow0.48 m3/s

Certification

  • Complete generating set is type-tested according to ISO 8528-8 standard.
  • The control panel is certified by an ISO 17025 accredited laboratory to have IP55 according to
    IEC 60355

Control Panel Specifications

Control Panel GMP260MKIII

GMP260MKIII (DSE6110 MKIII) panel is an automatic start generating set panel of microprocessor-based design capable of interfacing with electronic engines through CAN-bus J1939. It is fully configurable by PC software, and most settings can be programmed by front fascia buttons. If mains voltage is to be monitored, DSE6120MKIII can be offered. Circuit Breaker Schneider or ABB, 3 Pole MCB (4 Pole optional).

Construction

Sheet FabricationCNC shearing & bending
Paint typeHeat-treated powder-coated
Paint applicationElectrostatic corona spraying
Durability tests
  • Impact [EN ISO 6272]
  • Salt spray resistance [ASTM B117-73]
  • Humidity resistance [ASTM D2247]
Compliance
  • Panel compliant with [ISO8528-8]
  • Clearance & Creepage [IEC60355-1]
  • Leakage current & Dielectric strength [IEC60355-1]
  • Protection against electric shock [IEC600 364-4-41]
Degree of protectionIP55
Wire crimping
  • Crimping force up to 20 kN
  • Accuracy of 0.01 mm
  • Each crimp checked by Komax CFA+
Wire coding
  • Wires coded by color and cross-section
  • Wires coded by printed numbers
  • Wires coded by printed function of the wire

Panel Functions Matrix

Protection (standard)(Optional)Control (standard)(Optional)Instrumentation (standard)(Optional)
Over/Under AC VoltageHigh Oil TemperatureRemote Start InputBattery Charger: 5A, 10A, ULGen AC Voltage: 3ph VLL & VLNLube Oil Temperature
Over/Under FrequencyHigh Exhaust TemperatureEmergency Stop ButtonFuel Pump ControlGen Frequency: HzExhaust Temperature
Delayed Over CurrentLow Fuel PressureCommon Alarm Volt-Free ContactExtension: Ethernet-Modbus TCPGen Current: 3 phase AEngine Inlet Air (Boost) Pressure
Short-circuitLow Coolant PressureEvent Log (100 Events)RS485 – Modbus RTUPower: kW, kVA, kVAr & PFCharging Ammeter
Over kWLow Fuel LevelWeekly ExerciserGPS TrackerEnergy: kW·h, kVA·h, kVAr·hFuel Pressure
High Engine TemperatureLow Oil LevelAudible AlarmWater in Fuel DetectionLube Oil PressureCoolant Pressure
Low Oil PressureHigh Winding TemperatureStandard CANbus J1939Webnet ApplicationsEngine Coolant TemperatureFuel Level
Maintenance AlarmHigh Bearing TemperaturePre/Post Heat ControlSNMP GatewayBattery DC VoltageLube Oil Level
High/Low Battery VoltageLow Boost PressureData LoggingInputs: 20 mA, 10 VDC AlternatorWinding Temperature 3×RTD
Low Coolant Level (Note 2)Fusible Link Fire ProtectionPLC EditorThermocouplesEngine SpeedBearing Temperature RTD
3-ph Mains Sensing (6120)Low Coolant TemperatureOil Level ControlOperating HoursTier 4 Support

Note 1: Some optional features may be standard if CANbus is established within electronic engines.

Note 2: Low coolant level protection is standard for gensets above 200 kVA; otherwise optional.

Note 3: There is a limitation in the number of protections and measurements that can be offered with GMP260MK. Other control panels/modules can be offered per specification (DSE 7310/20, 7410/20, 8610, 8810, etc.).

Genset Standard Features

Assembly: Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528.

Fabrication:

  • Engine/alternator assembly rests on skid with anti-vibration mounting pads.
  • Skid made of durable sheet metals and beams exceeding vibration & torsion resistance norms.
  • Skid-mounted fuel tank with gauge, filler cap, inlet and outlet hoses.
  • Control panel enclosure made of reliable sheet metal.

Paint:

  • Skid and panel enclosure painted with heat-treated, powder-coated electrostatic corona spraying.
  • Durability tests passed:
    • Impact (EN ISO 6272)
    • Salt Spray Resistance (ASTM B117-73)
    • Humidity Resistance (ASTM D2247)

Works-Testing:

  • All gensets tested prior to dispatch.
  • Test auto-generated and checked according to ISO 8528.
  • Certificate issued for each genset.

Equipment:

  • Water-cooled radiator with belt-driven blower fan and full guarding
  • Electric starter with solenoid relay
  • Battery charging alternator
  • Energized-to-run solenoid
  • Replaceable fuel, oil and air filters
  • Heavy-duty lead-acid battery with matching capacity (Amps & CCA)
  • Industrial exhaust silencer – 16 dB noise reduction
  • Integral fuel tank with 342 L capacity

Documentation:

  • User Manual for operation, installation and maintenance
  • Wiring diagram
  • Test report
  • Maintenance schedule
  • Catalogues for Engine, Alternator & AVR

Genset Optional Features

  • Manual & Automatic Transfer Switches
  • Synchronizing & Totalizing Panels
  • Fuel water separator
  • Water jacket heater
  • Oil heater
  • Fuel heater
  • Battery heater
  • Anti-condensation Heater
  • Air Shut-off Valve
  • Oil Sampler
  • Pre-lube Oil Pump

Shipping Dimensions (Open Set):

  • Length: 2900 mm
  • Width: 1080 mm
  • Height: 1710 mm