Ghaddar Generators
powered by John Deere
John Deere has an unparalleled track record for
providing reliable, robust and efficient Engines that
won’t let you down, even in the most extreme conditions.
You can depend on a John Deere engine for uninterrupted performance, durability and unbeatable fuel economy. These engines are built tough, for our harsh ambient conditions.
Ghaddar Generators powered by John Deere


Engine Technical Data | ||
Make & Series Model / GSPU | JOHN DEERE 3029DF129 / 3029DFU29R | |
Cylinders & Arrangement | 3; vertical in-line | |
Bore & Stroke (mm) | 106 x 110 | |
Induction system | Naturally aspirated | |
Combustion | Direct injection | |
Cycle | 4 stroke | |
Compression ratio | 17.2:1 | |
Cooling System | Water cooled | |
Displacement | 2.9 liters | |
Lube oil capacity | 6.0 liters Max | |
Coolant capacity | 5.7 liters | |
Standard governor (Optional) | Mechanical (Electronic) | |
Engine Speed | 1500 rpm | |
Fuel & Oil Consumption | Fuel Cons. | Oil Cons. |
Consumption @ 100% Load (L/H) | 6.9 | 0.018 |
Consumption @ 75% Load (L/H) | 5.3 | 0.014 |
Consumption @ 50% Load (L/H) | 3.7 | 0.010 |
Consumption @ 25% Load (L/H) | 2.3 | 0.006 |
Radiator Cooling Air Flow (m3/s) | 2.0 | |
Emissions regulations | For non-regulated territories | |
Exhaust temperature ᵒC (max) | 610 | |
Max exhaust gas flow (m3/min) | 5.2 | |
Max. allowed back pressure (kPa) | 7.5 |
- Diesel Fuel is according to BS2869 Class A2 or equivalent.
- Lubricating oil is according to Grade SAE 15W-40 API CI4.
- The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data | |
Make & Model | Leroy Somer TAL042C |
Frequency / No. of poles | 50 Hz / 4P |
Ingress protection | IP23 |
Insulation class | H |
Terminals (Optional) | 6 (12) |
Excitation system | SHUNT |
Winding pitch | 2/3 |
AVR model | R120 |
Overspeed | 2250 R.P.M. |
Voltage regulation | ± 1 % |
Coolant air flow | 0.1 m3/s |
- The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Sheet Fabrication | CNC shearing & bending |
Paint type | Heat-treated powder-coated |
Paint application | Electrostatic corona spraying |
Durability tests | § IMPACT [EN ISO 6272]§ Salt spray resistance [ASTM B117-73] § Humidity Resistance [ASTM D2247] |
Compliance | § Panel is compliant with [ISO8528-8]§ Clearance & Creepage [IEC60355-1] § Leakage current & Dielectric strength [IEC60355-1] § Protection against electric shock [IEC600 364-4-41] |
Degree of protection | IP55 |
Wire crimping | § Crimping force up to 20KN§ Accuracy of 0.01mm § Each crimping is checked by Komax CFA+ |
Wire coding | § Wires are coded by wire color and cross-section§ Wires are coded by printed numbers § Wires are coded by printed function of the wire |
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
- The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT27 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT32S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Series Model / GSPU |
JOHN DEERE 3029DFG20 / 3029DFU20 |
|
Cylinders & Arrangement |
3; vertical in-line |
|
Bore & Stroke (mm) |
106 x 110 |
|
Induction system |
Naturally aspirated |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.2:1 |
|
Cooling System |
Water cooled |
|
Displacement |
2.9 liters |
|
Lube oil capacity |
6.0 liters Max |
|
Coolant capacity |
13 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
7.4 |
0.019 |
Consumption @ 75% Load (L/H) |
5.5 |
0.014 |
Consumption @ 50% Load (L/H) |
3.9 |
0.010 |
Consumption @ 25% Load (L/H) |
2.4 |
0.006 |
Radiator Cooling Air Flow (m3/s) |
2.0 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
610 |
|
Max exhaust gas flow (m3/min) |
5.2 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL042C |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.1 m3/s |
Certification
-
The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


Engine Technical Data | ||
Make & Series Model / GSPU | JOHN DEERE 3029DF129 / 3029DFU29 | |
Cylinders & Arrangement | 3; vertical in-line | |
Bore & Stroke (mm) | 106 x 110 | |
Induction system | Naturally aspirated | |
Combustion | Direct injection | |
Cycle | 4 stroke | |
Compression ratio | 17.2:1 | |
Cooling System | Water cooled | |
Displacement | 2.9 liters | |
Lube oil capacity | 6.0 liters Max | |
Coolant capacity | 5.7 liters | |
Standard governor (Optional) | Mechanical (Electronic) | |
Engine Speed | 1800 rpm | |
Fuel & Oil Consumption | Fuel Cons. | Oil Cons. |
Consumption @ 100% Load (L/H) | 8.0 | 0.021 |
Consumption @ 75% Load (L/H) | 6.4 | 0.017 |
Consumption @ 50% Load (L/H) | 4.5 | 0.012 |
Consumption @ 25% Load (L/H) | 2.7 | 0.007 |
Radiator Cooling Air Flow (m3/s) | 2.4 | |
Emissions regulations | For non-regulated territories | |
Exhaust temperature ᵒC (max) | 570 | |
Max exhaust gas flow (m3/min) | 6.1 | |
Max. allowed back pressure (kPa) | 7.5 |
- Diesel Fuel is according to BS2869 Class A2 or equivalent.
- Lubricating oil is according to Grade SAE 15W-40 API CI4.
- The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data | |
Make & Model | Leroy Somer TAL042C |
Frequency / No. of poles | 60Hz / 4P |
Ingress protection | IP23 |
Insulation class | H |
Terminals (Optional) | 6 (12) |
Excitation system | SHUNT |
Winding pitch | 2/3 |
AVR model | R120 |
Overspeed | 2250 R.P.M. |
Voltage regulation | ± 1 % |
oolant air flow | 0.13 m3/s |
- The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication | CNC shearing & bending |
Paint type | Heat-treated powder-coated |
Paint application | Electrostatic corona spraying |
Durability tests | § IMPACT [EN ISO 6272] § Salt spray resistance [ASTM B117-73] § Humidity Resistance [ASTM D2247] |
Compliance | § Panel is compliant with [ISO8528-8] § Clearance & Creepage [IEC60355-1] § Leakage current & Dielectric strength [IEC60355-1] § Protection against electric shock [IEC600 364-4-41] |
Degree of protection | IP55 |
Wire crimping | § Crimping force up to 20KN § Accuracy of 0.01mm § Each crimping is checked by Komax CFA+ |
Wire coding | § Wires are coded by wire color and cross-section § Wires are coded by printed numbers § Wires are coded by printed function of the wire |
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
- The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT30 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT36S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Series Model / GSPU |
JOHN DEERE 3029DFG20 / 3029DFU20 |
|
Cylinders & Arrangement |
3; vertical in-line |
|
Bore & Stroke (mm) |
106 x 110 |
|
Induction system |
Naturally aspirated |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.2:1 |
|
Cooling System |
Water cooled |
|
Displacement |
2.9 liters |
|
Lube oil capacity |
6.0 liters Max |
|
Coolant capacity |
13 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
8.0 |
0.022 |
Consumption @ 75% Load (L/H) |
6.4 |
0.017 |
Consumption @ 50% Load (L/H) |
4.4 |
0.012 |
Consumption @ 25% Load (L/H) |
2.7 |
0.007 |
Radiator Cooling Air Flow (m3/s) |
2.4 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
570 |
|
Max exhaust gas flow (m3/min) |
6.1 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL042C |
Frequency / No. of poles |
60Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
oolant air flow |
0.13 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Certification
-
The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT40 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT45S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 3029TFG20 / 3029TFU20 |
|
Cylinders & Arrangement |
3; vertical in-line |
|
Bore & Stroke (mm) |
106 x 110 |
|
Induction system |
Turbocharged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.2:1 |
|
Cooling System |
Water cooled |
|
Displacement |
2.9 liters |
|
Lube oil capacity |
6.0 liters Max |
|
Coolant capacity |
13 liters |
|
Standard governor |
Electronic |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
10.0 |
0.026 |
Consumption @ 75% Load (L/H) |
7.67 |
0.020 |
Consumption @ 50% Load (L/H) |
5.0 |
0.013 |
Consumption @ 25% Load (L/H) |
3.0 |
0.008 |
Radiator Cooling Air Flow (m3/s) |
1.7 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
440 |
|
Max exhaust gas flow (m3/min) |
7.3 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL042F |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.1 m3/s |
Certification
-
The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
- The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528-8 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT45 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT50S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 3029TFG20 / 3029TFU20 |
|
Cylinders & Arrangement |
3; vertical in-line |
|
Bore & Stroke (mm) |
106 x 110 |
|
Induction system |
Turbocharged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.2:1 |
|
Cooling System |
Water cooled |
|
Displacement |
2.9 liters |
|
Lube oil capacity |
6.0 liters Max |
|
Coolant capacity |
13 liters |
|
Standard governor |
Electronic |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
11.7 |
0.031 |
Consumption @ 75% Load (L/H) |
9.2 |
0.024 |
Consumption @ 50% Load (L/H) |
6.4 |
0.017 |
Consumption @ 25% Load (L/H) |
4.0 |
0.011 |
Radiator Cooling Air Flow (m3/s) |
2.1 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
414 |
|
Max exhaust gas flow (m3/min) |
9.4 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL042F |
Frequency / No. of poles |
60Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.13 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT60 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT66S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 3029HFG20 / 3029HFU20 |
|
Cylinders & Arrangement |
3; vertical in-line |
|
Bore & Stroke (mm) |
106 x 110 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
16.3:1 |
|
Cooling System |
Water cooled |
|
Displacement |
2.9 liters |
|
Lube oil capacity |
8.0 liters Max |
|
Coolant capacity |
12 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
13.8 |
0.042 |
Consumption @ 75% Load (L/H) |
10.4 |
0.032 |
Consumption @ 50% Load (L/H) |
7.0 |
0.021 |
Consumption @ 25% Load (L/H) |
3.9 |
0.013 |
Radiator Cooling Air Flow (m3/s) |
2.4 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
545 |
|
Max exhaust gas flow (m3/min) |
10.9 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL042H |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.1 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT70 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT75S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 4045TF120 / 4045TF158R |
|
Cylinders & Arrangement |
4; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
4.5 liters |
|
Lube oil capacity |
12 liters Max |
|
Coolant capacity |
18 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
16.0 |
0.042 |
Consumption @ 75% Load (L/H) |
12.3 |
0.032 |
Consumption @ 50% Load (L/H) |
8.0 |
0.021 |
Consumption @ 25% Load (L/H) |
5.0 |
0.013 |
Radiator Cooling Air Flow (m3/s) |
2.4 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
538 |
|
Max exhaust gas flow (m3/min) |
12.2 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL044B |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.25 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT80 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT88S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 4045TF220 / 4045TF258R |
|
Cylinders & Arrangement |
4; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
4.5 liters |
|
Lube oil capacity |
12 liters Max |
|
Coolant capacity |
25 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
17.5 |
0.060 |
Consumption @ 75% Load (L/H) |
13.6 |
0.043 |
Consumption @ 50% Load (L/H) |
9.1 |
0.024 |
Consumption @ 25% Load (L/H) |
4.6 |
0.013 |
Radiator Cooling Air Flow (m3/s) |
2.1 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
600 |
|
Max exhaust gas flow (m3/min) |
13.6 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL044B |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.25 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT80 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT88S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 4045TF120 / 4045TF158 |
|
Cylinders & Arrangement |
4; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
4.5 liters |
|
Lube oil capacity |
12 liters Max |
|
Coolant capacity |
8 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
18.5 |
0.049 |
Consumption @ 75% Load (L/H) |
14.5 |
0.038 |
Consumption @ 50% Load (L/H) |
10.0 |
0.026 |
Consumption @ 25% Load (L/H) |
6.0 |
0.016 |
Radiator Cooling Air Flow (m3/s) |
2.5 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
501 |
|
Max exhaust gas flow (m3/min) |
14.5 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL044B |
Frequency / No. of poles |
60Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.3 m3/s |
Certification
-
The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT90 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT100S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
-
This rating level at voltage 220/380 are achieved when upsizing alternator to TAL044D
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 4045TF220 / 4045TF258 |
|
Cylinders & Arrangement |
4; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
4.5 liters |
|
Lube oil capacity |
12 liters Max |
|
Coolant capacity |
25 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
21.0 |
0.055 |
Consumption @ 50% Load (L/H) |
16.0 |
0.042 |
Consumption @ 75% Load (L/H) |
11.0 |
0.029 |
Consumption @ 25% Load (L/H) |
6.3 |
0.017 |
Radiator Cooling Air Flow (m3/s) |
2.4 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
528 |
|
Max exhaust gas flow (m3/min) |
16.3 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
||
Make & Model |
Leroy Somer TAL044B |
Leroy Somer TAL044D |
Frequency / No. of poles |
60Hz / 4P |
60Hz / 4P |
Ingress protection |
IP23 |
IP23 |
Insulation class |
H |
H |
Terminals (Optional) |
6 (12) |
6 (12) |
Excitation system |
SHUNT |
SHUNT |
Winding pitch |
2/3 |
2/3 |
AVR model |
R120 |
R120 |
Overspeed |
2250 R.P.M. |
2250 R.P.M. |
Voltage regulation |
± 1 % |
± 1 % |
Coolant air flow |
0.3 m3/s |
0.3 m3/s |
Certification
-
The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT100 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT110S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 4045HFG20 - CD24978 |
|
Cylinders & Arrangement |
4; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
4.5 liters |
|
Lube oil capacity |
14.5 liters Max |
|
Coolant capacity |
16.5 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
22.2 |
0.060 |
Consumption @ 75% Load (L/H) |
16.7 |
0.043 |
Consumption @ 50% Load (L/H) |
11.7 |
0.029 |
Consumption @ 25% Load (L/H) |
6.3 |
0.014 |
Radiator Cooling Air Flow (m3/s) |
2.3 |
|
Emissions regulations |
Best Fuel Consumption |
|
Exhaust temperature ᵒC (max) |
525 |
|
Max exhaust gas flow (m3/min) |
18.8 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL044D |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.25 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT120 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT135S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 4045HFG20 |
|
Cylinders & Arrangement |
4; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged- Aftercooled |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
4.5 liters |
|
Lube oil capacity |
20.5 liters Max |
|
Coolant capacity |
17 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
27.7 |
0.070 |
Consumption @ 75% Load (L/H) |
21.2 |
0.053 |
Consumption @ 50% Load (L/H) |
14.9 |
0.037 |
Consumption @ 25% Load (L/H) |
7.4 |
0.020 |
Radiator Cooling Air Flow (m3/s) |
4.13 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
610 |
|
Max exhaust gas flow (m3/min) |
22.3 |
|
Max. allowed back pressure (kPa) |
7.1 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL044H |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.25 m3/s |
Certification
-
The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT125 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT135S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
-
This rating level at voltage 220/380 & 127/220 are achieved when upsizing alternator to TAL044H
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 4045HF120 / 4045HF158 |
|
Cylinders & Arrangement |
4; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
4.5 liters |
|
Lube oil capacity |
12 liters Max |
|
Coolant capacity |
25 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
27.5 |
0.072 |
Consumption @ 75% Load (L/H) |
21.0 |
0.055 |
Consumption @ 50% Load (L/H) |
13.5 |
0.036 |
Consumption @ 25% Load (L/H) |
7.5 |
0.020 |
Radiator Cooling Air Flow (m3/s) |
3.0 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
536 |
|
Max exhaust gas flow (m3/min) |
21.6 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Make & Model |
Leroy Somer TAL044D |
Leroy Somer TAL044H |
Frequency / No. of poles |
60Hz / 4P |
60Hz / 4P |
Ingress Protection |
IP23 |
IP23 |
Insulation class |
H |
H |
Terminals (Optional) |
6 (12) |
6 (12) |
Excitation System |
SHUNT |
SHUNT |
Winding Pitch |
2/3 |
2/3 |
AVR Model |
R120 |
R120 |
Overspeed |
2250 R.P.M. |
2250 R.P.M. |
Voltage Regulation |
± 1 % |
± 1 % |
Coolant air flow |
0.3 m3/s |
0.3 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT135 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT150S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6068TF220 / 6068TF258 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
6.8 liters |
|
Lube oil capacity |
19 liters Max |
|
Coolant capacity |
29 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
32.0 |
0.084 |
Consumption @ 75% Load (L/H) |
25.0 |
0.066 |
Consumption @ 50% Load (L/H) |
16.5 |
0.043 |
Consumption @ 25% Load (L/H) |
9.3 |
0.024 |
Radiator Cooling Air Flow (m3/s) |
2.8 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
569 |
|
Max exhaust gas flow (m3/min) |
24.2 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL044H |
Frequency / No. of poles |
60Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.3 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT150 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT165S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6068HFG20 CD24980 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
6.8 liters |
|
Lube oil capacity |
19.5 liters Max |
|
Coolant capacity |
22.5 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
34.0 |
0.088 |
Consumption @ 75% Load (L/H) |
25.4 |
0.066 |
Consumption @ 50% Load (L/H) |
17 |
0.044 |
Consumption @ 25% Load (L/H) |
8.4 |
0.02 |
Radiator Cooling Air Flow (m3/s) |
5.2 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
555 |
|
Max exhaust gas flow (m3/min) |
27.9 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to EN590 standard or equivalent..
-
Lubricating oil is according to Grade SAE 15W-40 API CI4 or CJ4..
-
The anti-freeze added should be compliant with ASTM D6210.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL044J |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.25 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump


The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT180 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT200S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6068HFG20 CD24981 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged- Aftercooled |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
6.8 liters |
|
Lube oil capacity |
32 liters Max |
|
Coolant capacity |
22.5 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
40.0 |
0.104 |
Consumption @ 75% Load (L/H) |
30.0 |
0.078 |
Consumption @ 50% Load (L/H) |
20.5 |
0.052 |
Consumption @ 25% Load (L/H) |
10 |
0.026 |
Radiator Cooling Air Flow (m3/s) |
5.2 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
593 |
|
Max exhaust gas flow (m3/min) |
32.7 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to EN590 standard or equivalent..
-
Lubricating oil is according to Grade SAE 15W-40 API CI4 or CJ4.
-
The anti-freeze added should be compliant with ASTM D6210.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL044L |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R120 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.29 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 342 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT185 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT205S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
-
This rating level at voltage 220/380 & 127/220 are achieved when upsizing alternator to TAL046B
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6068HF150 / 6068HF158 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
6.8 liters |
|
Lube oil capacity |
24.6 liters Max |
|
Coolant capacity |
29 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
42.0 |
0.110 |
Consumption @ 75% Load (L/H) |
32.0 |
0.084 |
Consumption @ 50% Load (L/H) |
21.0 |
0.055 |
Consumption @ 25% Load (L/H) |
11.0 |
0.029 |
Radiator Cooling Air Flow (m3/s) |
2.9 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
551 |
|
Max exhaust gas flow (m3/min) |
31.5 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|||
Make & Model |
Leroy Somer TAL044J |
Leroy Somer TAL046B |
|
Frequency / No. of poles |
60Hz / 4P |
60 Hz / 4P |
|
Ingress protection |
IP23 |
IP23 |
|
Insulation class |
H |
H |
|
Terminals (Optional) |
6 (12) |
6 (12) |
|
Excitation system |
SHUNT |
SHUNT |
|
Winding pitch |
2/3 |
2/3 |
|
AVR model |
R120 |
R150 |
|
Overspeed |
2250 R.P.M. |
2250 R.P.M. |
|
Voltage regulation |
± 1 % |
± 1 % |
|
Coolant air flow |
0.3 m3/s |
0.58 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 117 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT200 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT220S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6068HFG20 / 6068HFU20 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged & air-to-air after cooled |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
6.8 liters |
|
Lube oil capacity |
32 liters Max |
|
Coolant capacity |
27 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
44.7 |
0.118 |
Consumption @ 75% Load (L/H) |
35 |
0.092 |
Consumption @ 50% Load (L/H) |
23 |
0.060 |
Consumption @ 25% Load (L/H) |
11.5 |
0.030 |
Radiator Cooling Air Flow (m3/s) |
5.4 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
519 |
|
Max exhaust gas flow (m3/min) |
35.2 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL046B |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R150 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.48 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 342 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT200 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT220S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6068HF120 / 6068HF258 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
6.8 liters |
|
Lube oil capacity |
32 liters Max |
|
Coolant capacity |
27 liters |
|
Standard governor (Optional) |
Mechanical (Electronic) |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
47.0 |
0.124 |
Consumption @ 75% Load (L/H) |
36.0 |
0.095 |
Consumption @ 50% Load (L/H) |
23.5 |
0.062 |
Consumption @ 25% Load (L/H) |
12.5 |
0.033 |
Radiator Cooling Air Flow (m3/s) |
3.2 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
551 |
|
Max exhaust gas flow (m3/min) |
37.5 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL046B |
Frequency / No. of poles |
60Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R150 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.58 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 342 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3%
at the reference conditions equivalent to those specified in ISO 8528/1 standard.
Notes:
1. The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
2.This generating set is of fixed speed of 1800 rpm.
3.DT200 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
4.DT220S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
5.This rating level at voltage 220/380 are achieved when upsizing alternator to TAL046B
Engine Technical Data | ||
Make & Model / GSPU | JOHN DEERE 6068HFG20 / 6068HFU20 | |
Cylinders & Arrangement | 6; vertical in-line | |
Bore & Stroke (mm) | 106 x 127 mm | |
Induction system | Turbo Charged & air-to-air after cooled | |
Combustion | Direct injection | |
Cycle | 4 stroke | |
Compression ratio | 17.0:1 | |
Cooling System | Water cooled | |
Displacement | 6.8 liters | |
Lube oil capacity | 32 liters Max | |
Coolant capacity | 11.3 liters | |
Standard governor (Optional) | Mechanical (Electronic) | |
Engine Speed | 1800 rpm | |
Fuel & Oil Consumption | Fuel Cons. | Oil Cons. |
Consumption @ 100% Load (L/H) | 48.5 | 0.128 |
Consumption @ 75% Load (L/H) | 37 | 0.097 |
Consumption @ 50% Load (L/H) | 24.2 | 0.064 |
Consumption @ 25% Load (L/H) | 12.8 | 0.034 |
Radiator Cooling Air Flow (m3/s) | 5.6 | |
Emissions regulations | For non-regulated territories | |
Exhaust temperature ᵒC (max) | 463 | |
Max exhaust gas flow (m3/min) | 40.2 | |
Max. allowed back pressure (kPa) | 7.5 |
The above performance data are valid as per the following specs:
- Diesel Fuel is according to BS2869 Class A2 or equivalent.
- Lubricating oil is according to Grade SAE 15W-40 API CI4.
- The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data | ||
Make & Model | Leroy Somer TAL046A | Leroy Somer TAL046B |
Frequency / No. of poles | 60Hz / 4P | 60Hz / 4P |
Ingress protection | IP23 | IP23 |
Insulation class | H | H |
Terminals (Optional) | 6 (12) | 6 (12) |
Excitation system | SHUNT | SHUNT |
Winding pitch | 2/3 | 2/3 |
AVR model | R150 | R150 |
Overspeed | 2250 R.P.M. | 2250 R.P.M. |
Voltage regulation | ± 1 % | ± 1 % |
Coolant air flow | 0.58 m3/s | 0.58 m3/s |
Certification
- The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication | CNC shearing & bending |
Paint type | Heat-treated powder-coated |
Paint application | Electrostatic corona spraying |
Durability tests | § IMPACT [EN ISO 6272]
§ Salt spray resistance [ASTM B117-73] § Humidity Resistance [ASTM D2247] |
Compliance | § Panel is compliant with [ISO8528-8]
§ Clearance & Creepage [IEC60355-1] § Leakage current & Dielectric strength [IEC60355-1] § Protection against electric shock [IEC600 364-4-41] |
Degree of protection | IP55 |
Wire crimping | § Crimping force up to 20KN
§ Accuracy of 0.01mm § Each crimping is checked by Komax CFA+ |
Wire coding | § Wires are coded by wire color and cross-section
§ Wires are coded by printed numbers § Wires are coded by printed function of the wire |
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Certification
- The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 342 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT246 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT270S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6068HFG55 / 6068HFU55 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged & air-to-air after cooled |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.2:1 |
|
Cooling System |
Water cooled |
|
Displacement |
6.8 liters |
|
Lube oil capacity |
32.5 liters Max |
|
Coolant capacity |
33 liters |
|
Standard governor (Optional) |
Electronic |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
53 |
0.139 |
Consumption @ 75% Load (L/H) |
40 |
0.105 |
Consumption @ 50% Load (L/H) |
27 |
0.071 |
Consumption @ 25% Load (L/H) |
15 |
0.039 |
Radiator Cooling Air Flow (m3/s) |
4.9 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
523 |
|
Max exhaust gas flow (m3/min) |
37.3 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL046D |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R150 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.48 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 342 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT260 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT285S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
-
This rating level at voltage 220/380 is achieved when upsizing alternator to TAL046H
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6068HFG55 / 6068HFU55 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
106 x 127 mm |
|
Induction system |
Turbo Charged & air-to-air after cooled |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
17.2:1 |
|
Cooling System |
Water cooled |
|
Displacement |
6.8 liters |
|
Lube oil capacity |
32.5 liters Max |
|
Coolant capacity |
33 liters |
|
Standard governor (Optional) |
Electronic |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
53.0 |
0.139 |
Consumption @ 75% Load (L/H) |
41.0 |
0.108 |
Consumption @ 50% Load (L/H) |
28.0 |
0.074 |
Consumption @ 25% Load (L/H) |
15.5 |
0.041 |
Radiator Cooling Air Flow (m3/s) |
3.4 |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
468.5 |
|
Max exhaust gas flow (m3/min) |
41.9 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|||
Make & Model |
Leroy Somer TAL046D |
Leroy Somer TAL046H |
|
Frequency / No. of poles |
60Hz / 4P |
60Hz / 4P |
|
Ingress protection |
IP23 |
IP23 |
|
Insulation class |
H |
H |
|
Terminals (Optional) |
6 (12) |
6 (12) |
|
Excitation system |
SHUNT |
SHUNT |
|
Winding pitch |
2/3 |
2/3 |
|
AVR model |
R150 |
R150 |
|
Overspeed |
2250 R.P.M. |
2250 R.P.M. |
|
Voltage regulation |
± 1 % |
± 1 % |
|
Coolant air flow |
0.58 m3/s |
0.58 m3/s |
Certification
-
The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 342 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
300 kVA Generator Ghaddar Powered by John Deere
Ratings @ 0.8 PF |
Prime rating |
Stand-by rating |
|
Voltage*1 |
Frequency*2 |
DT300*3 |
DT330S*4 |
230/400 V |
50Hz |
300 kVA |
331 kVA |
The above ratings represent the 300 kVA Generator capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1500 rpm.
-
DT300 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT330S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6090HFG84 / 6090HFU84 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
118.4×136 mm |
|
Induction system |
Turbo Charged & air-to-air after cooled |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
16.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
9 liters |
|
Lube oil capacity |
40 liters Max |
|
Coolant capacity |
43 liters |
|
Standard governor |
Electronic |
|
Engine Speed |
1500 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
70.6 |
0.186 |
Consumption @ 75% Load (L/H) |
56.0 |
0.147 |
Consumption @ 50% Load (L/H) |
40.0 |
0.105 |
Consumption @ 25% Load (L/H) |
20.0 |
0.053 |
Radiator Cooling Air Flow (m3/s) |
TBA |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
547 |
|
Max exhaust gas flow (m3/min) |
57.7 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|
Make & Model |
Leroy Somer TAL046F |
Frequency / No. of poles |
50 Hz / 4P |
Ingress protection |
IP23 |
Insulation class |
H |
Terminals (Optional) |
6 (12) |
Excitation system |
SHUNT |
Winding pitch |
2/3 |
AVR model |
R150 |
Overspeed |
2250 R.P.M. |
Voltage regulation |
± 1 % |
Coolant air flow |
0.48 m3/s |
Certification
-
The complete generating set is type-tested according to ISO 8528-8 standard.
Control Panel Specifications
The 300 kVA Generator is equipped with
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Standard & Optional features of 300 KVA Generator
Protection (STANDARD) |
Control (STANDARD) |
Instrumentation (STANDARD) |
Over /Under AC voltage |
Remote start input |
Gen AC Voltage: 3ph VLL & VLN |
Over /Under frequency |
Emergency Stop button |
Gen Frequency: Hz |
Delayed Over current |
Common Alarm volt-free contact |
Gen Current: 3 phase A |
Short-circuit |
Event log (50 events) |
Power: KW, KVA, KVAR & PF |
Over KW |
Weekly Exerciser |
Energy: KWhr, KVAhr, KVARhr |
High Engine Temperature |
Audible Alarm |
Lube Oil pressure |
Low oil pressure |
Standard CANbus J1939 |
Engine coolant temperature |
Maintenance Alarm |
Preheat control |
Battery DC Voltage |
High/Low Battery voltage |
(OPTIONAL Note 1) |
DC Alternator Voltage |
Low coolant level Note 2 |
Ethernet –Modbus TCP RS485- Modbus RTU Webnet – GPS tracker
|
Engine Speed |
(OPTIONAL Note 1 ,3) |
Operating hours |
|
|
(OPTIONAL Note 1 , 3) |
|
|
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines.
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional.
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK.
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others).
Certification
-
The control panel is certified by an ISO17025 accredited laboratory to have IP55 according to IEC60355
300 KVA Generator Standard Features:
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
–The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– Moreover, The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– In addition, a skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– Moreover, The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 342 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
300 KVA Generator Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump
300 KVA Generator Shipping Data (Dimensions)
Shipping Data (Dimensions) – Open Set |
|||
Length – A |
Width – B |
Height – C |
Weight |
2900 mm |
1080 mm |
1710 mm |
2075 Kg |
You can shop online from the wide range of John Deere parts for 300 kVA Generator Ghaddar through Ghaddar online shop:
https://shop.ghaddar.com/product-category/john-deere-engines-parts/
The above ratings represent the generating set capability guaranteed within ±3% at the reference conditions equivalent to those specified in ISO 8528/1 standard.
NOTES
-
The applicable voltage range is 220V, 380V to 480V for 60Hz applications. For other voltages, please consult factory.
-
This generating set is of fixed speed of 1800 rpm.
-
DT320 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
-
DT350S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
-
This rating level at voltage 220/380 is achieved when upsizing alternator to TAL046H.
Engine Technical Data |
||
Make & Model / GSPU |
JOHN DEERE 6090HFG84 / 6090HFU84 |
|
Cylinders & Arrangement |
6; vertical in-line |
|
Bore & Stroke (mm) |
118.4×136 mm |
|
Induction system |
Turbo Charged & air-to-air after cooled |
|
Combustion |
Direct injection |
|
Cycle |
4 stroke |
|
Compression ratio |
16.0:1 |
|
Cooling System |
Water cooled |
|
Displacement |
9 liters |
|
Lube oil capacity |
40 liters Max |
|
Coolant capacity |
43 liters |
|
Standard governor |
Electronic |
|
Engine Speed |
1800 rpm |
|
Fuel & Oil Consumption |
Fuel Cons. |
Oil Cons. |
Consumption @ 100% Load (L/H) |
72.0 |
0.189 |
Consumption @ 75% Load (L/H) |
60.0 |
0.158 |
Consumption @ 50% Load (L/H) |
42.0 |
0.110 |
Consumption @ 25% Load (L/H) |
21.5 |
0.057 |
Radiator Cooling Air Flow (m3/s) |
TBA |
|
Emissions regulations |
For non-regulated territories |
|
Exhaust temperature ᵒC (max) |
499 |
|
Max exhaust gas flow (m3/min) |
58.5 |
|
Max. allowed back pressure (kPa) |
7.5 |
The above performance data are valid as per the following specs:
-
Diesel Fuel is according to BS2869 Class A2 or equivalent.
-
Lubricating oil is according to Grade SAE 15W-40 API CI4.
-
The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data |
|||
Make & Model |
Leroy Somer TAL046F |
Leroy Somer TAL046H |
|
Frequency / No. of poles |
60Hz / 4P |
60Hz / 4P |
|
Ingress protection |
IP23 |
IP23 |
|
Insulation class |
H |
H |
|
Terminals (Optional) |
6 (12) |
6 (12) |
|
Excitation system |
SHUNT |
SHUNT |
|
Winding pitch |
2/3 |
2/3 |
|
AVR model |
R150 |
R150 |
|
Overspeed |
2250 R.P.M. |
2250 R.P.M. |
|
oltage regulation |
± 1 % |
± 1 % |
|
Coolant air flow |
0.58 m3/s |
0.58 m3/s |
Control Panel Specifications
GMP260MKIII (DSE6110 MKIII) panel is an automatic
start generating set panel of microprocessor-based
design which is capable of interfacing with
electronic engine through the can-bus J1939. It is
fully configurable by PC software, yet most settings
can be programmed by front fascia buttons. If
Mains voltage is to be monitored, DSE6120MKIII
can be offered.
Circuit Breaker Schneider or ABB, 3 Pole MCB (4
Pole available as Optional)
Construction
Sheet Fabrication |
CNC shearing & bending |
Paint type |
Heat-treated powder-coated |
Paint application |
Electrostatic corona spraying |
Durability tests |
|
Compliance |
|
Degree of protection |
IP55 |
Wire crimping |
|
Wire coding |
|
Protection (standard) | (OPTIONAL Note 1,3) | Control (standard) | (OPTIONAL Note 1) | Instrumentation (standard) | (OPTIONAL Note 1,3) | |
Over /Under AC Voltage | High Oil Temperature | Remote Start Input | Battery Changer: 5A, 10A , UL | Gen AC Voltage: 3ph VLL & VLN | Lube Oil Temperature | |
Over /Under Frequency | High Exhaust Temperature | Emergency Stop Button | Fuel Pump Control | Gen Frequency: Hz | Exhaust Temperature | |
Delayed Over Current | Low Fuel Pressure | Common Alarm Volt-Free Contact | Extension: | Gen Current: 3 phase A | Engine Inlet air (Boost) pressure | |
Short-circuit | Low Coolant Pressure | Event Log (100 Events) | Ethernet-Modbus TCP | Power: KW, KVA, KVAR & PF | Charging Ammeter | |
Over KW | Low Fuel Level | Weekly Exerciser | RS485- Modbus RTU | Energy: KWhr, KVAhr, KVARhr | Fuel pressure | |
High Engine Temperature | Low Oil Level | Audible Alarm | GPS Tracker | Lube Oil Pressure | Coolant Pressure | |
Low Oil Pressure | High winding temperature | Standard CANbus J1939 | Water in Fuel Detection | Engine Coolant Temperature | Fuel level | |
Maintenance Alarm | High Bearing Temperature | Pre/Post Heat Control | Webnet Applications | Battery DC Voltage | Lube Oil Level | |
High/Low Battery Voltage | Low Boost Pressure | Data Logging | SNMP Gateway | DC Alternator | Winding temperature 3xRTD | |
Low coolant level (Note 2) | Fusible Link Fire Protection | PLC Editor | Inputs: 20mA, 10V | Engine Speed | Bearing Temperature RTD | |
3 ph Mains Sensing (6120) |
|
Oil Level Control | Thermocouples | Operating Hours | Tier 4 Support | |
Note 1: some OPTIONAL features could be standard if CANbus is established within electronic engines. | ||||||
Note 2: Low coolant level protection is standard feature for Gensets above 200KVA, otherwise it is optional. | ||||||
Note 3: There is limitation in the number of protections and measurements that can be offered with GMP260MK. | ||||||
Other types of control Panels & Modules can be offered according to required specifications (DSE 7310/20, 7410/20, 8610, 8810 and Others). |
Genset Standard Features
Assembly:
Gensets are assembled at Ghaddar Machinery Factory in compliance with ISO 8528 standard.
Fabrication:
– The engine/alternator assembly rests on skid with Anti-vibration mounting pads.
– The skid is made up of durable sheet metals and beams exceeding “Vibration & Torsion” Resistance Norms.
– A skid mounted fuel tank is supplied with fuel gauge, filler cap, fuel inlet and outlet hoses.
– The control panel enclosure is made up of reliable metal sheet.
Paint:
-The skid and control panel enclosure are painted with heat-treated and power-coated electrostatic corona spraying.
– Paints passed durability tests conforming to international quality standards.
– Impact (EN ISO 6272)
– Salt Spray Resistance (ASTM B117-73)
– Humidity Resistance (ASTM D2247)
Works-Testing:
– All Gensets are tested prior to dispatch.
– Test is automatically generated and checked according to ISO8528
– Test certificate is issued for each Genset
Equipment:
– Water cooled Radiator with belt driven blower fan and full guarding
– Electric starter with solenoid Relay
– Battery Charging Alternator
– Energized to run solenoid
– Replaceable fuel, oil and air filters
– Heavy duty leads acid battery with matching capacity (Amps & CCA)
– One loose supplied industrial exhaust silencer – 16 DB noise reduction level.
– Integral Fuel Tank with 342 L capacity.
Documentation:
– User Manual for Operation, Installation and Maintenance guidance
– Wring Diagram.
– Test Report
– Maintenance Schedule
– Catalogues for Engine, Alternator & AVR
Genset Optional Features
Manual & Automatic Transfer Switches,
Synchronizing & Totalizing Panels
Fuel water separator
Water jacket heater
Oil heater
Fuel heater
Battery heater
Anti-condensation Heater
Air Shut-off Valve
Oil Sampler
Pre-lube Oil Pump